留言板

尊敬的读者、作者、审稿人, 关于本刊的投稿、审稿、编辑和出版的任何问题, 您可以本页添加留言。我们将尽快给您答复。谢谢您的支持!

姓名
邮箱
手机号码
标题
留言内容
验证码

陆地和近海面大气光学湍流估算与测量

徐春燕 詹国伟 青春 蔡俊 吴晓庆

KozlovA, ParfenovYu, ChepelevV, 等. 电力系统运行状态下抗高压脉冲干扰评估[J]. 强激光与粒子束, 2019, 31: 070006. doi: 10.11884/HPLPB201931.180356
引用本文: 徐春燕, 詹国伟, 青春, 等. 陆地和近海面大气光学湍流估算与测量[J]. 强激光与粒子束, 2018, 30: 021003. doi: 10.11884/HPLPB201830.170296
Kozlov A, Parfenov Yu, Chepelev V, et al. Assessing immunity of power systems to effects of high-voltage pulses with power on[J]. High Power Laser and Particle Beams, 2019, 31: 070006. doi: 10.11884/HPLPB201931.180356
Citation: Xu Chunyan, Zhan Guowei, Qing Chun, et al. Estimation and measurement of optical turbulence over land and offshore[J]. High Power Laser and Particle Beams, 2018, 30: 021003. doi: 10.11884/HPLPB201830.170296

陆地和近海面大气光学湍流估算与测量

doi: 10.11884/HPLPB201830.170296
基金项目: 

国家自然科学基金项目 41576185

详细信息
    作者简介:

    徐春燕(1993—),女,硕士研究生,从事大气光学湍流估算和测量的研究; xuchunya@mail.ustc.edu.cn

    通讯作者:

    吴晓庆(1963—),男,研究员,博士生导师,主要从事大气边界层、大气湍流测量与模式、天文选址等研究; xqwu@aiofm.ac.cn

  • 中图分类号: P183.4

Estimation and measurement of optical turbulence over land and offshore

  • 摘要: 基于Monin-Obukhov相似性理论,采用MARIAH算法,利用成都和茂名两个地区、两个高度层上的温度、湿度、风速等常规气象参数估算折射率结构常数,并对估算值与温度脉动仪测量值进行比较分析。结果显示:利用常规气象参数估算得到的成都与茂名的折射率结构常数在变化趋势及量级上基本符合温度脉动仪测量值。成都和茂名的折射率结构常数估算值与测量值的相关系数分别为0.86与0.92,平均绝对值偏差分别为0.410与0.414。因此,采用MARIAH算法估算陆地和近海面大气光学折射率结构常数是可行的;茂名中午时刻的折射率结构常数峰值比成都大一个量级。
  • There is an opinion that the most sensitive to the effects of pulse disturbances are the technical systems incorporating semiconductor devices, while high-voltage equipment is immune against them. This conclusion is based on the results of tests of high-voltage equipment when the operating voltage has not been simulated (power off). But even short duration voltage pulses, such as those created by HEMP or HPEM threats, are capable to initiate a spark short circuit. This short circuit can outgrow into an arc flashover under the effect of the operating voltage. As a result, the destruction of insulators and the failure of the high-voltage equipment can take place. Such effects can lead to catastrophic phenomena in power supply systems. Therefore, it is important to investigate flashovers and damages of power supply system elements due to high voltage pulses with power on and power off. A set of publications were devoted to the investigation. For example, the results of investigation of flashovers and damages of power line insulators due to high voltage pulses with power on and power off are described in Refs.[1-4]. These investigations have shown that high-voltage insulators could be destroyed as a result of joint action of a pulse disturbance and operation voltage of a power line.

    However, insulators are not the most important elements of power systems. High-voltage transformers are much more important and expensive elements. Our thoughts concerning ways of transformer test to joint action of pulse disturbance and operating voltage of a high-voltage power line are presented in this article.

    This test can be performed using the equipment developed for testing insulators of high-voltage power supply lines. General view of the experimental setup is shown in Fig. 1. The setup consists of two simulators, namely, a high-voltage pulse simulator and a power line operating voltage simulator.

    Figure  1.  General view of the experimental setup

    A block-diagram of the high-voltage pulse simulator is presented in Fig. 2. Basic elements of the simulator are: charger, capacitor store with controlled discharger, high-voltage generator, generator of delayed pulses (delayed-pulse oscillator), and ignition device.

    Figure  2.  Block-diagram of the high-voltage pulse simulator

    A high-voltage pulse being formed by this simulator acts onto a device under test (DUT).Capacitive voltage divider, current transformer, optical isolator, as well as digital oscilloscope are used for measuring parameters of the simulated pulses. The charger is intended to charge the capacitive storage up to a certain voltage. By changing this voltage from 3 kV up to 20 kV, it is possible to change amplitude of a high-voltage pulse from 60 kV up to 400 kV.

    After start of the controlled discharger the capacitor storage is discharging on the high-voltage generator, which forms a pulse with necessary parameters.

    The generator of delayed pulses controls the work of the ignition device and starts the digital oscilloscope. Besides, it controls the work of the ignition system of the power line voltage simulator. Thus, a high-voltage pulse may be timed to occur at any point of waveform of a power line operating voltage.

    As a source of high-voltage pulses the generator based on exploding wires was used. This generator is shown in Fig. 3. It consists of the inductance and the block of exploding wires. Explosion of conductors occurs in the cylindrical chamber with a diameter of 60 mm and a length of 1550 mm. It was filled with nitrogen at pressure up to 1 MPa. Copper wires with a diameter of 40, 50 and 80 μm were used in experiments. Parameters of a generated pulse can be changed by means of changing the diameter and quantity of exploding wires.

    Figure  3.  Pulse generator based on exploding wires

    The generator based on exploding wires forms the pulse with the following parameters: peak voltage 60-400 kV; rise time 30-100 ns; pulse duration 50-500 ns. The waveform of generated pulse is shown in Fig. 4.

    Figure  4.  Waveform of the generated pulse

    The block-diagram of the test equipment used to reproduce a power line operating voltage is shown in Fig. 5.

    Figure  5.  Simulator of power line operating voltage

    The basic element of the simulator of a power line operating voltage is the air-core pulse transformer. Fig. 6 shows the air-core transformer. It forms a voltage with an effective frequency from 30 Hz up to 100 Hz.

    Figure  6.  Air-core transformer

    By changing the voltage of the capacitance storage one can control the amplitude of the reproduced power line operating voltage. Waveforms of a current in the primary winding of the air-core transformer and an open-circuit voltage in its secondary winding are presented in Fig. 7.

    Figure  7.  Current (I) in primary winding and the open-circuit voltage (U) in secondary winding of the air-core transformer

    The open-circuit voltage of the transformer has an amplitude of 15 kV when the voltage of the charger is equal to 3 kV. The open-circuit voltage delays on 90° from the current in primary winding of the air-core transformer.

    Required amplitude of the power line current may be reproduced in the secondary short-circuit winding. Waveforms of the current in the primary winding and the short-circuit current in the secondary winding are presented in Fig. 8. One can see that the current in the primary winding is about 10 kA. In this case the short-circuit current in the secondary winding is about 1 kA. This current will be a current of arc after overlapping of the DUT. Currents in the primary and secondary windings are in phase. Thus, the line operating voltage and the arc current will be 90° out of phase at power-on testing.

    Figure  8.  Currents in windings of the transformer at short circuit

    Control pulses of the delayed pulse generator start ignition systems of the high-voltage pulse simulator and the power line operating voltage simulator. Thus, time delay between the high-voltage pulse and maximum of the line operating voltage may be in range from several microseconds up to several milliseconds.

    To measure parameters of the reproduced pulses and to register processes of DUT overlapping the following measuring tools are used:

    — Digital oscilloscope;

    — Digital camera (exposition time is 0.03 ms, shooting frequency is 300 Hz);

    — Rogovski coil;

    — Capacity divider (rise time 5 ns, factor of division 1∶350 000);

    — Fiberoptic line;

    — Resistive high-voltage divider.

    Photos of the resistive high-voltage divider and the capacity divider are presented in Fig. 9 and Fig. 10.

    Figure  9.  Resistive high-voltage divider
    Figure  10.  Capacity divider

    It is necessary to remind that the experimental setup described above has been used for high-voltage insulators tests. Naturally, the scheme of transformers tests should be different, as is shown in Fig. 11.

    Figure  11.  Transformers test scheme based on the equipment developed for insulators test

    Apparently, this scheme does not need comments as it is analogous to the scheme of insulators tests described above. However, it should be noted that it has a shortcoming: only one phase is being exposed to influence of test pulses. The schemes overcoming this shortcoming are presented in the following section.

    The first variant of the transformer test with the use of a serial 10 kV diesel-generator is shown in Fig. 12. Besides the diesel-generator, this scheme includes three high-voltage generators and a device for their synchronization.

    Figure  12.  Scheme of the transformer test by means of a diesel-generator and three high-voltage generators

    This scheme is much simpler in realization in comparison with the previous one, as it does not demand building of the simulator of an operating voltage for the high-voltage power line. However it has two shortcomings, one is that the extremely powerful high-voltage diesel-generator must be used, the other consists in using three synchronously functioning generators of high voltage pulses. It is possible to eliminate this difficulty by using the optimized scheme shown in Fig. 13.

    Figure  13.  Scheme of the transformer test by means of a diesel-generator and influencing loop circuit

    Practical application of the optimized scheme shows that it is the simplest in realization in comparison with the other two of the three schemes. Yet it still has shortcomings. The main shortcoming is that the maximum voltage concerning the earth which can be induced by means of an influencing circuit does not exceed 100 kV.

    The previous researches showed that joint action of a high-voltage pulse disturbance and an operating voltage of a power line leads to destruction of insulators of this line. This fact testifies about need of assessing immunity of other elements of power infrastructure to similar influences. A set of ways which can be used for test of high-voltage transformers is presented in the article. One of them is similar to the way used for test of insulators. It includes the high-voltage pulse simulating an electric disturbance and the pulse which simulates operating voltage of a power line being given to the transformer. The main shortcoming of this way is high cost of the simulator of the line operating voltage. For this reason, as a rule, only one phase of the transformer is being tested.

    In the article two more ways of tests, free from this shortcoming, are offered. They allow applying the testing pulses to three phases simultaneously. A high-voltage pulse disturbance is simulated by means of three generators or by means of the loop circuit with a current which induces disturbances in all wires of the line simultaneously. An operating voltage of the line is simulated by means of the high power diesel-generator.

  • 图  1  近地面测量系统

    Figure  1.  Schematic diagram of surface layer measurement system

    图  2  成都Cn2的温度脉动仪测量值与模式估算值的比较

    Figure  2.  Time series comparison of Cn2 estimated by model and measured by micro-thermometer in Chengdu from May 16 to May 18, 2014

    图  3  茂名Cn2的温度脉动仪测量值与模式估算值的比较

    Figure  3.  Time series comparison of Cn2 estimated by model and measured by micro-thermometer in Maoming from October 20 to October 22, 2012

    图  4  成都与茂名Cn2的温度脉动仪测量值与估算值的统计分析

    Figure  4.  Statistical analysis of model and measurement of Cn2 in Chengdu and Maoming

    表  1  近地面大气参数测量系统传感器技术参数

    Table  1.   Technical parameters of sensors for near-surface atmospheric parameters measurement

    name model accuracy
    temperature/RH probe HMP155 temperature: < 0.1 ℃;RH: ±1% RH(0~90%RH), ±1.7%RH(90%~100%RH)
    wind monitor 05106 wind speed: ±0.3 m/s, wind direction: ±3°
    micro-thermometer MT1 system noise level corresponding to DT of 2×10-3
    下载: 导出CSV
  • [1] 吴晓庆, 朱行听, 黄宏华, 等. 基于Monin-Obukhov相似理论估算近地面光学湍流强度[J]. 光学学报, 2012, 32 (7): 22-28. https://www.cnki.com.cn/Article/CJFDTOTAL-GXXB201207003.htm

    Wu Xiaoqing, Zhu Xingting, Huang Honghua, et al. Optical turbulence of atmospheric surface layer estimated based on the Monin-Obukhov similarity theory. Acta Optica Sinica, 2012, 32 (7): 22-28 https://www.cnki.com.cn/Article/CJFDTOTAL-GXXB201207003.htm
    [2] 李杨, 相里斌, 张文喜. 湍流大气中激光传输对傅里叶望远镜成像质量的影响[J]. 强激光与粒子束, 2013, 25 (2): 292-296. doi: 10.3788/HPLPB20132502.0292

    Li Yang, Xiang Libin, Zhang Wenxi. Effects of laser propagation through atmospheric turbulence on imaging quality in Fourier telescopy. High Power Laser and Particle Beams, 2013, 25 (2): 292-296 doi: 10.3788/HPLPB20132502.0292
    [3] Kunkel K E, Walters D L. Modeling the diurnal dependence of the optical refractive index structure parameter[J]. Journal of Geophysical Research: Oceans, 1983, 88 (C15): 10999-11004. doi: 10.1029/JC088iC15p10999
    [4] Sadot D, Kopeika N S. Forecasting optical turbulence strength on the basis of macroscale meteorology and aerosols: Models and validation[J]. Optical Engineering, 1992, 31 (2): 200-212. doi: 10.1117/12.56059
    [5] 青春, 吴晓庆, 李学彬, 等. 基于天气数值预报模式预报高空光学湍流[J]. 强激光与粒子束, 2015, 27: 061009. doi: 10.11884/HPLPB201527.061009

    Qing Chun, Wu Xiaoqing, Li Xuebin. Forecast upper air optical turbulence based on weather research and forecasting model. High Power Laser and Particle Beams, 2015, 27: 061009 doi: 10.11884/HPLPB201527.061009
    [6] Thiermann V, Lohse H, Englisch G. Modeling optical turbulence in the atmospheric boundary layer over sea[C]//Proc of SPIE. 1997, 2596: 198-203.
    [7] Hutt D L. Modeling and measurements of atmospheric optical turbulence over land[J]. Optical Engineering, 1999, 38 (8): 1288-1295. doi: 10.1117/1.602188
    [8] 戴福山, 李有宽. 利用气象要素估算海洋大气近地层光学湍流[J]. 光学学报, 2007, 27 (2): 191-196. https://www.cnki.com.cn/Article/CJFDTOTAL-GXXB200702001.htm

    Dai Fushan, Li Youkuan. Estimation of the optical turbulence in the marine atmospheric surface layer based on meteorological data. Acta Optica Sinica, 2007, 27 (2): 191-196 https://www.cnki.com.cn/Article/CJFDTOTAL-GXXB200702001.htm
    [9] Rachele H, Tunick A, Hansen F V. MARIAH—A similarity-based method for determining wind, temperature, and humidity profile structure in the atmospheric surface layer[J]. Journal of Applied Meteorology, 1995, 34 (4): 1000-1005. doi: 10.1175/1520-0450(1995)034<1000:MASBMF>2.0.CO;2
    [10] Qing Chun, Wu Xiaoqing, Huang Honghua, et al. Estimating the surface layer refractive index structure constant over snow and sea ice using Monin-Obukhov similarity theory with a mesoscale atmospheric model[J]. Optics Express, 2016, 24 (18): 20424. doi: 10.1364/OE.24.020424
  • 期刊类型引用(1)

    1. 秦锋,陈伟,王旭桐,任书庆,黄涛,聂鑫. 强电磁脉冲下金属氧化物避雷器瞬态响应特性. 高电压技术. 2022(08): 3326-3333 . 百度学术

    其他类型引用(0)

  • 加载中
图(4) / 表(1)
计量
  • 文章访问数:  1221
  • HTML全文浏览量:  283
  • PDF下载量:  221
  • 被引次数: 1
出版历程
  • 收稿日期:  2017-07-17
  • 修回日期:  2017-09-11
  • 刊出日期:  2018-02-15

目录

/

返回文章
返回